Refrigerant reclamation

Last updated

Refrigerant reclamation is the act of processing used refrigerant gas which has previously been used in some type of refrigeration loop such that it meets specifications for new refrigerant gas. In the United States, the Section 608 of the Clean Air Act of 1990 requires that used refrigerant be processed by a certified reclaimer, which must be licensed by the United States Environmental Protection Agency (EPA), and the material must be recovered and delivered to the reclaimer by EPA-certified technicians. [1]

Contents

Background

Coolant and refrigerants are found throughout the industrialized world, in homes, offices, and factories, in devices such as refrigerators, air conditioners, central air conditioning systems (HVAC), freezers, and dehumidifiers. When these units are serviced, there is a risk that refrigerant gas will be vented into the atmosphere, hence the creation of technician training and certification programs in order to ensure that the material is conserved and managed safely. Mistreatment of these gases has been shown to deplete the ozone layer and is suspected to contribute to global warming. [2]

Reclamation of used refrigerant by an EPA-certified reclaimer is required in order to sell used refrigerant not originating from and intended for use with motor vehicle air conditioners and stationary equipment like air conditioners, refrigerators, central air conditioning systems (HVAC), and other cooling equipment. The EPA implemented a Code of Federal Regulations in 1995 [3] in order to develop actions to meet the agreements defined in the Montreal Protocol.

Reclamation, as it refers to refrigerants, is one of three components in a refrigerant management process.

The EPA defines refrigerant reclamation as "Reclaim refrigerant means to reprocess refrigerant to at least the purity specified in appendix A to 40 CFR part 82, subpart F (based on AHRI Standard 700–1993, Specifications for Fluorocarbon and Other Refrigerants) and to verify this purity using the analytical methodology prescribed in appendix A. In general, reclamation involves the use of processes or procedures available only at a reprocessing or manufacturing facility." [4]

EPA establishes rules and regulations that reclaimers must acknowledge, and they license these reclaimers to operate. In most cases wholesale distributors provide this service as an intermediary, since they have such great resources to manage distribution.

The EPA requires that refrigerant be reclaimed when a certified technician recovers refrigerant and puts it in a special DoT container and has no intention of putting it back in the same system from which it was recovered.

Certification program

The final rule published on May 14, 1993, requires that refrigerant sold to a new owner be reclaimed to the AHRI Standard 700 of purity by a certified reclaimer (Sec. 82.154(g) and (h) referencing standard in Sec. 82.164 and the definition of reclaim found in Sec. 82.152). As discussed in the final rule, this requirement protects the purity of used refrigerant to prevent damage to air-conditioning and refrigeration equipment from the use of contaminated refrigerant. Equipment damage from contaminated refrigerant would result in costs to equipment owners, in releases of refrigerant from damaged equipment through increased leakage, servicing and replacement, and in reduction in consumer confidence in the quality of used refrigerant. This reduction in consumer confidence could lead to the premature retirement or retrofit of CFC or HCFC equipment since consumers would no longer believe that a sufficient stock of trustworthy refrigerants was available. [5]

AHRI develops standards and manages third party testing and certification programs. AHRI oversees the ARI reclaimer program: Refrigerant Testing Laboratory Certification Find ARI Performance Certified Refrigerant Testing Laboratory Certification.

The certification program includes verification for all participating refrigerant testing laboratories, performing ARI-700 testing on any new or reclaimed refrigerants.

Certified ratings

AHRI also works with many participants in the industry to ensure that the standards that reclaimers are expected to achieve are well defined and support the highest level of integrity so technicians can be confident in the materials they are using and installing.

Before reclamation can begin the material must be recovered and the EPA defines that as "Recover refrigerant means to remove refrigerant in any condition from an appliance and to store it in an external container without necessarily testing or processing it in any way."

Some circumstances where the material is being put back into the system it was removed and not being transferred to a new system the material can be recycled and the EPA defines that as "Recycle refrigerant means to extract refrigerant from an appliance and clean refrigerant for reuse without meeting all of the requirements for reclamation. In general, recycled refrigerant is refrigerant that is cleaned using oil separation and single or multiple passes through devices, such as replaceable core filter-driers, which reduce moisture, acidity, and particulate matter. These procedures are usually implemented at the field job site."

See also

Related Research Articles

<span class="mw-page-title-main">Chlorofluorocarbon</span> Class of organic compounds commonly used as refrigerants

Chlorofluorocarbons (CFCs) and hydrochlorofluorocarbons (HCFCs) are fully or partly halogenated hydrocarbons that contain carbon (C), hydrogen (H), chlorine (Cl), and fluorine (F), produced as volatile derivatives of methane, ethane, and propane.

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

The California Air Resources Board is an agency of the government of California that aims to reduce air pollution. Established in 1967 when then-governor Ronald Reagan signed the Mulford-Carrell Act, combining the Bureau of Air Sanitation and the Motor Vehicle Pollution Control Board, CARB is a department within the cabinet-level California Environmental Protection Agency.

<span class="mw-page-title-main">Refrigerant</span> Substance in a refrigeration cycle

A refrigerant is a working fluid used in the refrigeration cycle of air conditioning systems and heat pumps where in most cases they undergo a repeated phase transition from a liquid to a gas and back again. Refrigerants are heavily regulated due to their toxicity, flammability and the contribution of CFC and HCFC refrigerants to ozone depletion and that of HFC refrigerants to climate change.

Difluoromethane, also called difluoromethylene, HFC-32Methylene Fluoride or R-32, is an organic compound of the dihalogenoalkane variety. It has the formula of CH2F2. It is a colorless gas in the ambient atmosphere and is slightly soluble in the water, with a high thermal stability. Due to the low melting and boiling point, (-136.0 °C and -51.6 °C respectively) contact with this compound may result in frostbite. In the United States, the Clean Air Act Section 111 on Volatile Organic Compounds (VOC) has listed difluoromethane as an exception (since 1997) from the definition of VOC due to its low production of tropospheric ozone. Difluoromethane is commonly used in endothermic processes such as refrigeration or air conditioning.

Propane refrigeration is a type of compression refrigeration. Propane (R290) has been used successfully in industrial refrigeration for many years, and is emerging as an increasingly viable alternative for homes and businesses. Propane's operating pressures and temperatures are well suited for use in air conditioning equipment, but because of propane’s flammability, great care is required in the manufacture, installation and servicing of equipment that uses it as a refrigerant.

1,1,1,2-Tetrafluoroethane (also known as norflurane (INN), R-134a, Klea®134a,Freon 134a, Forane 134a, Genetron 134a, Green Gas, Florasol 134a, Suva 134a, or HFC-134a) is a hydrofluorocarbon (HFC) and haloalkane refrigerant with thermodynamic properties similar to R-12 (dichlorodifluoromethane) but with insignificant ozone depletion potential and a lower 100-year global warming potential (1,430, compared to R-12's GWP of 10,900). It has the formula CF3CH2F and a boiling point of −26.3 °C (−15.34 °F) at atmospheric pressure. R-134a cylinders are colored light blue. A phaseout and transition to HFO-1234yf and other refrigerants, with GWPs similar to CO2, began in 2012 within the automotive market.

Chlorodifluoromethane or difluoromonochloromethane is a hydrochlorofluorocarbon (HCFC). This colorless gas is better known as HCFC-22, or R-22, or CHClF
2
. It was commonly used as a propellant and refrigerant. These applications were phased out under the Montreal Protocol in developed countries in 2020 due to the compound's ozone depletion potential (ODP) and high global warming potential (GWP), and in developing countries this process will be completed by 2030. R-22 is a versatile intermediate in industrial organofluorine chemistry, e.g. as a precursor to tetrafluoroethylene.

R-410A, sold under the trademarked names AZ-20, EcoFluor R410, Forane 410A, Genetron R410A, Puron, and Suva 410A, is a zeotropic but near-azeotropic mixture of difluoromethane (CH2F2, called R-32) and pentafluoroethane (CHF2CF3, called R-125) that is used as a refrigerant in air conditioning and heat pump applications. R-410A cylinders were colored rose but are no longer specially color-coded, now bearing a standard light gray color.

Design for the Environment (DfE) is a design approach to reduce the overall human health and environmental impact of a product, process or service, where impacts are considered across its life cycle. Different software tools have been developed to assist designers in finding optimized products or processes/services. DfE is also the original name of a United States Environmental Protection Agency (EPA) program, created in 1992, that works to prevent pollution, and the risk pollution presents to humans and the environment. The program provides information regarding safer chemical formulations for cleaning and other products. EPA renamed its program "Safer Choice" in 2015.

<span class="mw-page-title-main">Clean Air Act (United States)</span> United States federal law to control air pollution

The Clean Air Act (CAA) is the United States' primary federal air quality law, intended to reduce and control air pollution nationwide. Initially enacted in 1963 and amended many times since, it is one of the United States' first and most influential modern environmental laws.

The Air Conditioning, Heating, and Refrigeration Institute (AHRI), formed in 2008 by a merger of the Air-Conditioning and Refrigeration Institute (ARI) and the Gas Appliance Manufacturers Association (GAMA), is a North American trade association of manufacturers of air conditioning, heating, and commercial refrigeration equipment.

Section 608 of the Clean Air Act serves as the main form of occupational licensure for technicians in the heating, ventilation, and air conditioning (HVAC) industry in the United States. The law requires that all persons who maintain, service, repair or dispose of appliances that contain regulated refrigerants be certified in proper refrigerant handling techniques. The regulatory program helps to minimize the release of refrigerants, and in particular ozone depleting refrigerants such as chlorofluorocarbons and hydrofluorocarbons, as well as other regulated refrigerants as determined by Section 612. The licensure program complies with the requirements under the Montreal Protocol. The Environmental Protection Agency (EPA) published implementing regulations at 40 CFR Part 82.

<span class="mw-page-title-main">Air quality law</span> Type of law

Air quality laws govern the emission of air pollutants into the atmosphere. A specialized subset of air quality laws regulate the quality of air inside buildings. Air quality laws are often designed specifically to protect human health by limiting or eliminating airborne pollutant concentrations. Other initiatives are designed to address broader ecological problems, such as limitations on chemicals that affect the ozone layer, and emissions trading programs to address acid rain or climate change. Regulatory efforts include identifying and categorising air pollutants, setting limits on acceptable emissions levels, and dictating necessary or appropriate mitigation technologies.

Daikin Applied Americas is a corporation that designs, manufacturers and sells heating, ventilation, and air conditioning (HVAC) products, systems, parts and services for commercial buildings. Since 2006, McQuay has been a subsidiary of Daikin Industries, Ltd. McQuay world headquarters are located in Minneapolis, Minnesota, United States. Products are sold by a global network of sales representatives and distributors.

<span class="mw-page-title-main">Pentafluoroethane</span> Chemical compound

Pentafluoroethane is a fluorocarbon with the formula CF3CHF2. Pentafluoroethane is currently used as a refrigerant (known as R-125) and also used as a fire suppression agent in fire suppression systems.

<span class="mw-page-title-main">1-Chloro-1,1-difluoroethane</span> Chemical compound

1-Chloro-1,1-difluoroethane (HCFC-142b) is a haloalkane with the chemical formula CH3CClF2. It belongs to the hydrochlorofluorocarbon (HCFC) family of man-made compounds that contribute significantly to both ozone depletion and global warming when released into the environment. It is primarily used as a refrigerant where it is also known as R-142b and by trade names including Freon-142b.

Life Cycle Climate Performance (LCCP) is an evolving method to evaluate the carbon footprint and global warming impact of heating, ventilation, air conditioning (AC), refrigeration systems, and potentially other applications such as thermal insulating foam. It is calculated as the sum of direct, indirect, and embodied greenhouse gas (GHG) emissions generated over the lifetime of the system “from cradle to grave,” i.e. from manufacture to disposal. Direct emissions include all climate forcing effects from the release of refrigerants into the atmosphere, including annual leakage and losses during service and disposal of the unit. Indirect emissions include the climate forcing effects of GHG emissions from the electricity powering the equipment. The embodied emissions include the climate forcing effects of the manufacturing processes, transport, and installation for the refrigerant, materials, and equipment, and for recycle or other disposal of the product at end of its useful life.

The Significant New Alternatives Policy is a program of the EPA to determine acceptable chemical substitutes, and establish which are prohibited or regulated by the EPA. It also establishes a program by which new alternatives may be accepted, and promulgates timelines to the industry regarding phase-outs of substitutes.

References

  1. Section 608 of the Clean Air Act of 1990
  2. Emissions of Greenhouse Gases Report by the US Department of Energy
  3. Code of Federal Regulations: Protection of Stratospheric Ozone
  4. Protection of Stratospheric Ozone: Supplemental Rule Regarding a Recycling Standard Under Section 608 (Proposed) of the Clean Air Act
  5. Protection of Stratospheric Ozone: Direct-Final Rulemaking Temporarily Extend the Existing Requirements