Transformer oil

Last updated

Transformer oil or insulating oil is an oil that is stable at high temperatures and has excellent electrical insulating properties. It is used in oil-filled wet transformers, [1] some types of high-voltage capacitors, fluorescent lamp ballasts, and some types of high-voltage switches and circuit breakers. Its functions are to insulate, suppress corona discharge and arcing, and to serve as a coolant.

Contents

Transformer oil is most often based on mineral oil, but alternative formulations with different engineering or environmental properties are growing in popularity.

Function and properties

Oil transformer with air convection cooled heat exchangers in the front and at the side Transformator Biomasseheizkraftwerk Steyr.JPG
Oil transformer with air convection cooled heat exchangers in the front and at the side

Transformer oil's primary functions are to insulate and cool a transformer. It must therefore have high dielectric strength, thermal conductivity, and chemical stability, and must keep these properties when held at high temperatures for extended periods. [2] Typically, they have a flash point greater than 140 °C (284 °F), pour point less than −40 °C (−40 °F), and a dielectric breakdown at greater than 28 kVRMS. [3] To improve cooling of large power transformers, the oil-filled tank may have external radiators through which the oil circulates by natural convection. Power transformers with capacities of thousands of kilovolt-ampere may also have cooling fans, oil pumps, and even oil-to-water heat exchangers. [4]

Power transformers undergo prolonged drying processes, using electrical self-heating, the application of a vacuum, or both to ensure that the transformer is completely free of water vapor before the insulating oil is introduced. This helps prevent corona formation and subsequent electrical breakdown under load.

Oil filled transformers with a conservator oil reservoir may have a gas detector relay like a Buchholz relay. These safety devices detect the buildup of gas inside the transformer due to corona discharge, overheating, or an internal electric arc. On a slow accumulation of gas, or rapid pressure rise, these devices can trip a protective circuit breaker to remove power from the transformer. Transformers without conservators are usually equipped with sudden pressure relays, which perform a similar function as the Buchholz relay.

Mineral oil alternatives

Mineral oil is generally effective as a transformer oil, but it has some disadvantages, one of which is its relatively low flashpoint versus some alternatives. If a transformer leaks mineral oil, it can potentially start a fire. Fire codes often require that transformers inside buildings use a less flammable liquid, or the use of dry-type transformers with no liquid at all. Mineral oil is also an environmental contaminant, and its insulating properties are rapidly degraded by even small amounts of water. Transformers are well equipped to keep water outside the oil for this reason.

Pentaerythritol tetra fatty acid synthetic and natural esters have emerged as an increasingly common mineral oil alternative, especially in high-fire-risk applications such as indoors due to their high fire point, which are over 300 °C (572 °F). [5] They are biodegradable, but however are more expensive than mineral oil. Natural esters have lower oxidation stability in the 120C oxygen saturated test of approximately 48-hours compared to 500-hours for Mineral oils, and are therefore used in closed transformers.

Hermetic seals are important for larger transformers due to thermal expansion and contraction. Mid-size and large power transformers will typically have a conservator and employ a rubber bag with the use of natural ester to reduce oxygen ingress and prevent the natural ester from experiencing a faster oxidation than utilities are accustomed to with mineral oils. Silicone or fluorocarbon-based oils, which are even less flammable, are also used, but they are more expensive than esters, and not biodegradable.[ citation needed ]

A 380 kV transformer with vegetable oil Kandelweg Umspanner.jpg
A 380 kV transformer with vegetable oil

There are over 3 million transformers with vegetable-based formulations, using soy or rapeseed based formulations in up to 500 kV transformers so far. However, coconut oil based formulations are unsuitable for use in cold climates or for voltages over 230 kV. [7] Researchers are also investigating nanofluids for transformer use; these would be used as additives to improve the stability and thermal and electrical properties of the oil. [8]

Polychlorinated biphenyls (PCBs)

Polychlorinated biphenyls (PCB) are synthetic dielectrics first made over a century ago and found to have desirable properties that led to their widespread use. [9] Polychlorinated biphenyls were formerly used as transformer oil, since they have high dielectric strength and are not flammable. Unfortunately, they are also toxic, bioaccumulative, not at all biodegradable, and difficult to dispose of safely. When burned, they form even more toxic products, such as chlorinated dioxins and chlorinated dibenzofurans.

Beginning in the 1970s, production and new uses of PCBs were banned in many countries, due to concerns about the accumulation of PCBs and toxicity of their byproducts. For instance, in the USA, production of PCBs was banned in 1979 under the Toxic Substances Control Act. [10] In many countries significant programs are in place to reclaim and safely destroy PCB contaminated equipment.[ citation needed ] One method that can be used to reclaim PCB contaminated transformer oil is the application of a PCB removal system, also called a PCB dechlorination system.

PCB removal systems use an alkali dispersion to strip the chlorine atoms from the other molecules in a chemical reaction. This forms PCB-free transformer oil and a PCB-free sludge. The two can then be separated via a centrifuge. The sludge can be disposed as regular non-PCB industrial waste. The treated transformer oil is fully restored, meeting the required standards, without any detectable PCB content. It can, thus, be used as the insulating fluid in transformers again. [11]

PCBs and mineral oil are miscible in all proportions, and sometimes the same equipment (drums, pumps, hoses, and so on) was used for either type of liquid, so PCB contamination of transformer oil continues to be a concern. For instance, under present regulations, concentrations of PCBs exceeding 5 parts per million can cause an oil to be classified as hazardous waste in California. [12]

Testing and oil quality

Transformer oils are subject to electrical and mechanical stresses while a transformer is in operation. In addition there is contamination caused by chemical interactions with windings and other solid insulation, catalyzed by high operating temperature. The original chemical properties of transformer oil change gradually, rendering it ineffective for its intended purpose after many years. [13] Oil in large transformers and electrical apparatus is periodically tested for its electrical and chemical properties, to make sure it is suitable for further use. Sometimes oil condition can be improved by filtration and treatment. Tests can be divided into:

  1. Dissolved gas analysis
  2. Furan analysis
  3. PCB analysis
  4. General electrical & physical tests:
    • Color & Appearance
    • Breakdown Voltage
    • Water Content
    • Acidity (Neutralization Value)
    • Dielectric Dissipation Factor
    • Resistivity
    • Sediments & Sludge
    • Flash Point
    • Pour Point
    • Density
    • Kinematic Viscosity

The details of conducting these tests are available in standards released by International Electrotechnical Commission, ASTM International, International standard, British Standards, and testing can be done by any of the methods. The Furan and DGA tests are specifically not for determining the quality of transformer oil, but for determining any abnormalities in the internal windings of the transformer or the paper insulation of the transformer, which cannot be otherwise detected without a complete overhaul of the transformer. Suggested intervals for these test are:

On-site testing

Some transformer oil tests can be carried out in the field, using portable test apparatus. Other tests, such as dissolved gas, normally require a sample to be sent to a laboratory. Electronic on-line dissolved gas detectors can be connected to important or distressed transformers to continually monitor gas generation trends.

To determine the insulating property of the dielectric oil, an oil sample is taken from the device under test, and its breakdown voltage is measured on-site according to the following test sequence:

See also

Related Research Articles

<span class="mw-page-title-main">Insulator (electricity)</span> Material that does not conduct an electric current

An electrical insulator is a material in which electric current does not flow freely. The atoms of the insulator have tightly bound electrons which cannot readily move. Other materials—semiconductors and conductors—conduct electric current more easily. The property that distinguishes an insulator is its resistivity; insulators have higher resistivity than semiconductors or conductors. The most common examples are non-metals.

<span class="mw-page-title-main">Transformer</span> Device to couple energy between circuits

A transformer is a passive component that transfers electrical energy from one electrical circuit to another circuit, or multiple circuits. A varying current in any coil of the transformer produces a varying magnetic flux in the transformer's core, which induces a varying electromotive force (EMF) across any other coils wound around the same core. Electrical energy can be transferred between separate coils without a metallic (conductive) connection between the two circuits. Faraday's law of induction, discovered in 1831, describes the induced voltage effect in any coil due to a changing magnetic flux encircled by the coil.

In physics, the term dielectric strength has the following meanings:

<span class="mw-page-title-main">Mineral oil</span> Liquid mixture of higher alkanes from a mineral source, particularly a distillate of petroleum

Mineral oil is any of various colorless, odorless, light mixtures of higher alkanes from a mineral source, particularly a distillate of petroleum, as distinct from usually edible vegetable oils.

<span class="mw-page-title-main">Hydraulic fluid</span> Medium to transfer power in hydraulic machinery

A hydraulic fluid or hydraulic liquid is the medium by which power is transferred in hydraulic machinery. Common hydraulic fluids are based on mineral oil or water. Examples of equipment that might use hydraulic fluids are excavators and backhoes, hydraulic brakes, power steering systems, automatic transmissions, garbage trucks, aircraft flight control systems, lifts, and industrial machinery.

In electrical engineering, partial discharge (PD) is a localized dielectric breakdown (DB) of a small portion of a solid or fluid electrical insulation (EI) system under high voltage (HV) stress. While a corona discharge (CD) is usually revealed by a relatively steady glow or brush discharge (BD) in air, partial discharges within solid insulation system are not visible.

<span class="mw-page-title-main">Lichtenberg figure</span> Branching shapes

A Lichtenberg figure, or Lichtenberg dust figure, is a branching electric discharge that sometimes appears on the surface or in the interior of insulating materials. Lichtenberg figures are often associated with the progressive deterioration of high voltage components and equipment. The study of planar Lichtenberg figures along insulating surfaces and 3D electrical trees within insulating materials often provides engineers with valuable insights for improving the long-term reliability of high-voltage equipment. Lichtenberg figures are now known to occur on or within solids, liquids, and gases during electrical breakdown.

<span class="mw-page-title-main">Electrical breakdown</span> Conduction of electricity through an insulator under sufficiently high voltage

In electronics, electrical breakdown or dielectric breakdown is a process that occurs when an electrically insulating material, subjected to a high enough voltage, suddenly becomes a conductor and current flows through it. All insulating materials undergo breakdown when the electric field caused by an applied voltage exceeds the material's dielectric strength. The voltage at which a given insulating object becomes conductive is called its breakdown voltage and, in addition to its dielectric strength, depends on its size and shape, and the location on the object at which the voltage is applied. Under sufficient voltage, electrical breakdown can occur within solids, liquids, or gases. However, the specific breakdown mechanisms are different for each kind of dielectric medium.

<span class="mw-page-title-main">High voltage</span> Electrical potential which is large enough to cause damage or injury

High voltage electricity refers to electrical potential large enough to cause injury or damage. In certain industries, high voltage refers to voltage above a certain threshold. Equipment and conductors that carry high voltage warrant special safety requirements and procedures.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

In electric power distribution and transmission, a Buchholz relay is a safety device mounted on some oil-filled power transformers and reactors, equipped with an external overhead oil reservoir called a "conservator".

<span class="mw-page-title-main">Electrical treeing</span>

In electrical engineering, treeing is an electrical pre-breakdown phenomenon in solid insulation. It is a damaging process due to partial discharges and progresses through the stressed dielectric insulation, in a path resembling the branches of a tree. Treeing of solid high-voltage cable insulation is a common breakdown mechanism and source of electrical faults in underground power cables.

Dissolved gas analysis (DGA) is an examination of electrical transformer oil contaminants. Insulating materials within electrical equipment liberate gases as they slowly break down over time. The composition and distribution of these dissolved gases are indicators of the effects of deterioration, such as pyrolysis or partial discharge, and the rate of gas generation indicates the severity. DGA is beneficial to a preventive maintenance program.

A silicone oil is any liquid polymerized siloxane with organic side chains. The most important member is polydimethylsiloxane. These polymers are of commercial interest because of their relatively high thermal stability and their lubricating properties.

<span class="mw-page-title-main">Sulfur hexafluoride circuit breaker</span> Switching device used in high voltage power grids

Sulfur hexafluoride circuit breakers protect electrical power stations and distribution systems by interrupting electric currents, when tripped by a protective relay. Instead of oil, air, or a vacuum, a sulfur hexafluoride circuit breaker uses sulfur hexafluoride (SF6) gas to cool and quench the arc on opening a circuit. Advantages over other media include lower operating noise and no emission of hot gases, and relatively low maintenance. Developed in the 1950s and onward, SF6 circuit breakers are widely used in electrical grids at transmission voltages up to 800 kV, as generator circuit breakers, and in distribution systems at voltages up to 35 kV.

A dielectric gas, or insulating gas, is a dielectric material in gaseous state. Its main purpose is to prevent or rapidly quench electric discharges. Dielectric gases are used as electrical insulators in high voltage applications, e.g. transformers, circuit breakers, switchgear, radar waveguides, etc.

A liquid dielectric is a dielectric material in liquid state. Its main purpose is to prevent or rapidly quench electric discharges. Dielectric liquids are used as electrical insulators in high voltage applications, e.g. transformers, capacitors, high voltage cables, and switchgear. Its function is to provide electrical insulation, suppress corona and arcing, and to serve as a coolant.

Condition monitoring of transformers in electrical engineering is the process of acquiring and processing data related to various parameters of transformers to determine their state of quality and predict their failure. This is done by observing the deviation of the transformer parameters from their expected values. Transformers are the most critical assets of electrical transmission and distribution systems, and their failures could cause power outages, personal and environmental hazards, and expensive rerouting or purchase of power from other suppliers. Identifying a transformer which is near failure can allow it to be replaced under controlled conditions at a non-critical time and avoid a system failure.

Transformer oil, a type of insulating and cooling oil used in transformers and other electrical equipment, needs to be tested periodically to ensure that it is still fit for purpose. This is because it tends to deteriorate over time. Testing sequences and procedures are defined by various international standards, many of them set by ASTM. Transformer oil testing consists of measuring breakdown voltage and other physical and chemical properties of samples of the oil, either in a laboratory or using portable test equipment on-site.

References

  1. Frank D. Petruzella, Industrial Electronics, p. 51, Glencoe/McGraw-Hill, 1996 ISBN   0028019962.
  2. Gill, Paul (2009). Electrical power equipment maintenance and testing (2nd ed.). Boca Raton: CRC Press. p. 193. ISBN   978-1-57444-656-2.
  3. Hirschler, Marcelo M. (2000). Electrical insulating materials : international issues (Online ed.). West Conshohocken, Pa.: ASTM. pp. 82–95. ISBN   978-0-8031-2613-8.
  4. Kenneth R. Edwards, Transformers, American Technical Publishers Ltd., 1996 ISBN   0-8269-1603-1 pp.138-14
  5. "Fluids Comparison". Midel.
  6. "Siemens has produced the world's first large-scale transformer that uses vegetable oil".
  7. "Coconut Oil As An Alternative To Transformer Oil" (PDF). ERU Symposium. November 2001. Archived from the original (PDF) on 2015-09-23. Retrieved 2013-08-08.
  8. n'Cho, J. S.; Loiselle, L.; Fofana, I.; Beroual, A.; Aka-Ngnui, T. (2010). "Parameters affecting the electrical and thermal properties of transformer oils". Parameters affecting the electrical and thermal properties of transformer_oils. Conference on Electrical Insulation and Dielectric Phenomena. pp. 1–4. doi:10.1109/CEIDP.2010.5723967. ISBN   978-1-4244-9468-2. S2CID   22800355 . Retrieved 6 February 2022.
  9. "PCB-RS Series – PCB Removal System | HERING VPT: The standard in oil purification and transformer drying technology" . Retrieved 2020-05-20.
  10. Blackmore, Carolyn. "Classification and Handling of PCB Waste" (PDF). Lawrence Berkeley National Laboratory. Retrieved 20 October 2017.
  11. "PCB Dechlorination System". Hering-VPT GmbH. Retrieved 20 October 2017.
  12. California Code of Regulations, Title 22, section 66261
  13. "Transformer Oil Deterioration and Degradation - Why is transformer oil purification essential?".